|
|
HI-Deluxe Installation Manual
|
Read this manual before beginning to install the solar system.
You will save installation time and get maximum performance
from the system.
|
Warning
If you plan to install the solar system on a roof you must
be experienced in working on a roof and have the proper safety
equipment. If not, you should hire a qualified person to install
it for you. Failure to observe proper safety procedures when
climbing ladders or working on a roof or other raised structure
can result in a fall with serious injury to you. Do not build
a supporting rack for the solar collectors against a pool
fence in such a way that children can climb the rack and thereby
gain access to the pool.
|
Planning
Before beginning installation check to see that the system
sizing and location criteria in the Solar System Selection
Guide have been followed. If you find it necessary to undersize
the system it is your responsibility to inform the pool owner
to expect proportionally less heat to the pool than if the
pool was sized according to the manufacturer's specifications.
For example, ten percent undersized means approximately ten
percent less heat to the pool.
|
|
|
Section 1: Mounting Components
This section provides descriptions and part number of Harter
Industries Installation Kits required for each solar pool
heating system. The mounting location of each kit component
is shown by the corresponding circled number in the Mounting
Components Diagram.
|
|
|
1. HI-Deluxe Collector Kit (Part No. 1090-2)
Contains all parts needed to fasten down one solar collector
and connect it to the next one in a row. You need one collector
kit per collector. Included is: 1 Outlet Header Hold-Down
Bracket Assembly (#2264), 2 Step Brackets (#8016-2), 2 Collector
Coupling Hoses (3 3/4" long, #8017-3), 4 Stainless Steel
Coupling Clamps (#1012).
|
2. Deluxe system Kit (Part No. 1091-2)
Contains parts needed to fasten down collectors, and to connect
piping to a system. Use one system kit for each row of collectors
in the installation. Included is: 1 Outlet Header Hold-Down
Bracket Assembly (#2264), 4 Hold-Down Strap Clamp Assembly
(#8023-1), 1 End Cap (#4032-2), 2 Pipe to Collector Adapter
(#4033), 2 Strap Brackets (#8016-2), 2 System Coupling Hoses
(6" long, #8017-6), 4 Stainless Steel Coupling Clamps
(#1012).
|
3. Hold-Down Strap
A hold-down strap is required to secure collectors to the
mounting surface. Use strap 4037-6 (54') for rows of up to
6 collectors or strap 4037-9 (80') for rows of up to 9 collectors
or 4037-14 (122') for rows of up to 14 collectors.
|
4. HI-Deluxe Split row Kit (Part No. 1093-2)
Use this kit whenever it is necessary to split a row of collectors
to clear obstructions, or to install part of a row on another
roof. Included: 1 Outlet Header Hold-Down Bracket Assembly
(#2264), 4 Hold-Down Strap Clamp Assembly (# 8023-1), 4 Pipe
to Collector Adapters (#4033), 2 Strap Brackets (#8016-2),
2 System Coupling Hoses (6" long, #8017-6), 4 Stainless
Steel Coupling Clamps, (#1012).
|
5. Header Inserts (Part No. 8029)
Heater Inserts are used in special situations where unusually
high stagnation temperatures are expected, such as in a desert
climate or where abnormally high system pressures may occur.
|
6. Vacuum Relief Valve Kit (Part No. 1094A)
One per system is required whenever collector inlet (bottom)
headers are higher than three feet above the pool surface
and with six or more collectors.
|
7. Check Valve
One check valve should be installed per system whenever collector
inlet (bottom) headers are more than three feet above the
pool.
|
8. Control System
Every HI-Deluxe pool heater needs a control system to by-pass
the solar collectors when the pool reaches the desired temperature,
or during inclement weather. In most climates an automatic
control system should be used. It consists of an electronic
control panel, two sensors and a motor-driven valve. In warm
climates, with little rain a manual control valve may be used.
|
Section 2 - Installation of HI-Deluxe Solar
Collectors
|
|
Step 1: Plan the location of the collectors on the
mounting surface. The outlet (top) headers must be at least
8 inches higher than the inlet (bottom) headers and the row
of collectors must slope at least ¼-inch per collector
toward the supply pipe as shown in Figure 1. That will allow
drainage that prevents freeze damage. Table B shows the amount
of space needed for an uninterrupted row of collectors. Add
8 to 12 inches at each end of the row for piping. Add 2 ½
inches above the outlet header for Mounting Brackets.
Note from Figure 1 that the pipe carrying the water back to
the pool (the return pipe) is connected to the collectors
diagonally opposite the supply pipe to the collectors. Determine
the position of the last outlet header hold-down bracket for
the row of collectors. Mark this point on the roof. The collector
outlet headers will be approximately 1" below this mark.
See Figure 3. From the mark, snap a chalk line to the opposite
end of the row. The chalk line must slope down the roof toward
the supply side ¼" per collector. For example,
six collectors in the row means a total slope of 1 ½
inches. See Figure 1. Using a 1/8" drill bit, drill a
hole for the first outlet header bracket on the first roof
mark. Measure up 1" on center from the first pilot hole
and drill pilot hole for second screw. See Figure 4. Repeat
this process all along the chalk line every 51 inches for
the number of collectors to be installed.
|
|
|
|
|
 |
|
Step 2: Inject a generous amount of high quality silicone
or urethane sealant into each hole and onto the surrounding
roof surface. Bolt all the outlet header hold-down brackets
to the roof as shown in Figure 4.
|
|
Figure 4:
|
|
Step 3: Locate the hold-down strap bracket holes using
the information in Table A. Measuring from the top outlet
header bracket chalk line, snap another chalk line parallel
to this line using the "A" dimension. The "B"
dimension is the same for all collector sizes. It is 16"
up from the outside of the bottom header and you can measure
it after the collectors are installed. Wait until after the
collectors are installed before installing the hold-down strap
brackets so as not to damage the collectors when you are bringing
them to the roof for installation
|
|
Figure 5:
|
| TABLE B - array
width |
| # of Collectors |
Width of Array |
| 5 |
21' |
| 6 |
25'6" |
| 7 |
29'9" |
| 8 |
34' |
| 9 |
38'3" |
| 10 |
42'6" |
| 11 |
46'9" |
| 12 |
51' |
|
|
Step 4: Bring the first collector to the roof and
slip the proper hoses over both ends of the inlet and outlet
headers on the last return collector. Make sure that the side
of the collector with the serial number label on it is facing
down. The long hoses go on the outlet of the last collector
and the inlet of the first collector. Push the hose onto the
collector header until it stops at the hose locating shoulder,
but NOT OVER it. Install a hose clamp 3/8" from the end
of the hose in order to center it on the header groove. The
clamp screw must face up so it will be accessible for tightening
and will not rub against the mounting surface. Make sure you
securely tighten each clamp with a nut driver. If a nut driver
is not available, a "hex" wrench or screwdriver
will suffice. THE HOSE CLAMPS MUST BE LOCATED OVER THE GROOVES
IN THE HEADER.
|
|
Step 5: Position the collector on the roof so that
the centers of the outlet connection hoses are directly beneath
the secured outlet header brackets and slip the bracket hold-down
clamps over the connection hoses. Lightly tighten the clamp
around the header hose. Refer to Figure 5. Continue to install
all the collectors in the array, coupling them side to side.
|
|
Step 6: Go to the lower chalk line previously snapped
on the roof for the hold-down strap brackets. Mark a hole
2" from the side of the first collector and continue
marking holes on the chalk line centered exactly between the
absorber surfaces until you reach the last collector. Mark
the last hole the same 2" to the side of the last collector.
Drill a pilot hole and apply sealant at each of these locations.
Bolt the hold-down strap brackets on the roof. It is OK to
step on the collectors as long as you stay one foot away from
the top and bottom headers. Mark the holes for the bottom
hold down strap by measuring up 16" from the outside
of the bottom header, centering them between the absorbers
and 2" away from the first and last collectors.
|
|
Step 7: Slip one end of the hold-down strap through
a strap clamp, then through the two slots in the hold-down
strap bracket at the end of the row. Pull about 3" of
the strap through and bend it back toward the clamp. Slip
the end the strap through the strap clamp and pull it tight.
Tighten the clamp screw securely, but do not over-tighten
it to the point where the clamp is distorted. Bring the strap
long free end across the collector face, passing through both
slots in the bracket located on the other side of the collector.
Pull the strap taut against the face of the collector. Repeat
this procedure for the remaining hold down strap, then connect
it to the hold-down strap bracket at the end as you did at
the first one.
|
|
Step 8: Install the vacuum relief valve in the outlet
header. at the opposite end of the row that is connected to
the collector outlet pipe. Refer to figures.
|
|
Step 9: Install an end cap in the inlet header of
each row, opposite the end that is connected to the collector
inlet pipe. Refer to Figures 1 and 2.
|
|
Warning: Do not attach mounting brackets to both headers
of a panel. Doing so voids warranty. The reason for this is
that the panel expands and contracts with changes in temperature.
With brackets on both headers, falling temperature causes
the panel to shrink, creating a strong force that can damage
the panel. Install the mounting brackets on the outlet header
only. That allows the inlet header to move slightly, adjusting
to changing temperatures.
|
|
Step 10: Connect collector headers to the supply and
return pipes with long hoses, coupling clamps and pipe to
collector adapters. Use only universal PVC/CPVC/ABS cement
between the adapter and the pipe fitting.
|
|
Step 11: It is important that you install the solar
system so that it can fully drain by gravity to prevent freeze
damage. The HI-Deluxe Automatic Control and Manual Control
Valves supplied by Harter Industries have a small built in
by-pass to allow water to slowly drain back to the pool, even
if the solar system is shut off. Therefore, collectors and
piping must slope toward the supply as shown in figure 1.
If you cannot plumb your system so that it will drain to the
supply, you must install a manual drain from the lowest point
in the system on the roof.
|
|
Step 12: INSPECT THE INSTALLATION AND CHECK ALL CLAMPS
FOR PROPER POSITION AND TIGHTNESS.
|
Section 3 - Stem Piping
|
|
To achieve optimum performance from the system, meet the
recommended water flow rates in Table C. Solar systems with
less than 300 square feet of collector area and located less
than 20 feet from the pool may be connected with 1 ½"
schedule 40 PVC pipe. All other systems should be plumbed
with 2" or larger schedule 40 PVC pipe. Plan the piping
to minimize the number of fittings. It is important to keep
pressure losses low so the maximum amount of water flows through
the collectors.
|
| Table C |
| Collector Size |
4x8 |
4x10 |
4x12 |
| Recommended Flow Rate Per Collector (GPM) |
3.2 |
4.0 |
5.0 |
| Minimum Flow Rate Per Collector (GPM) |
2.0 |
2.5 |
3.0 |
| Maximum Number of Collectors per Row |
16 |
15 |
14 |
|
|
Referring to Figures 1 and 2, note the supply to the solar
collectors is always at the inlet headers and the return is
diagonally opposite, at the outlet headers. The three-way
control valve, whether it is manual or motor driven is installed
in the inlet line to the collectors.
If the collectors are installed with the inlet headers more
than three feet higher than the pool, a check valve should
be installed between the pool filter and the control valve.
This valve prevents back-washing filter debris to the pool
when the pump shuts off.
The pool water sensor for an automatic control must be installed
before the control valve, so that it senses the actual pool
water temperature. Drill a 3/8-inch diameter hole in one side
of the filter system pipe anywhere between the filter and
solar system control valve. Insert the sensor and hold it
in place with the hose clamp.
Use a screw to attach the solar sensor to the same surface
to which the solar collectors are attached. Make sure that
the solar sensor sees the same amount of sun for the same
length of time as the collectors. Do not allow the solar sensor
to touch a solar collector or any pipe. Installation instructions
packed with the automatic control system should be followed.
Solar system isolation valves are optional and are not supplied
in standard kits.
If a high-pressure pool cleaner pump is used, its supply should
be connected between the filter and the control valve. If
a gas or electric heater or heat pump is used, it must be
installed between the solar system return tee and the return
line to the pool.
Heaters and heat pumps often create an excessive pressure
loss, so it is good practice to provide a bypass as shown.
The bypass valve may be opened whenever the solar system alone
is heating the pool (Note: some heaters require water flow
at all times).
On the roof (or other mounting surface) horizontal pipes should
be supported every 4 feet and vertical pipes every 8 feet.
A support should be placed as close to the collector supply
and return as is practical. HI-Deluxe Stainless Steel Hold
Down Clamps, Part No.2264, are useful for this purpose.
|
|
Special System layout Piping:
The shape of the available space or roof obstructions often
requires dividing a system into multiple rows or splitting
rows. Figure 7 below shows a system divided into two rows.
You will need a HI-Deluxe System Kit, Part No. 1091-2, for
each added row. Note the return from the lower row is connected
to the return at the highest point in the system. Slope the
rows toward the supply for drainage. Figure 8 on page 7 shows
a more complex, multi-level system with split rows. Roof vents
can often be straddled by using a pair of long hoses in place
of short ones. In Figure 8, the third row is on another roof,
higher than the first two rows. Note that the returns for
the first two rows meet the return from the third row at the
highest point in the system. Again, slope all rows toward
the supplies, so the system can drain.
|
|
|
|
|
|
|
With a roof vent pipe up to 3" in diameter, the collectors
can be positioned on either side of the vent. You can use
two system connector hoses (Part #8017-6) to couple the collectors
together for vent pipes or other obstacles up to 7" in
diameter. With obstructions of over 7" such as attic
fans and skylights, lay out the collectors on either side
of the obstruction using a HI-Deluxe Split Row Kit (Part #1093-2)
|
Section 4 - Start Up & Maintenance
|
|
Before starting the pump, we recommend that you install a
flow meter in a location to accurately show the flow rate
through the solar system. The preferred location is before
the solar collectors, after at least 3 feet of straight pipe.
You can then determine if the flow rate meets the level shown
in Table C.
This section describes the steps for starting an automatic
system. If a manual control is used, turn the three-way valve
to the indicated positions. The "OFF" mark opposite
the valve handle indicates the line that is blocked by the
diverter.
Switch the control to "ON". The Power and Heating
lights should come on and the control valve should turn to
divert water flow through the solar collectors. If it does
not, check the low voltage wiring to the valve motor. If the
valve motor has a toggle switch, make sure it is not in the
"OFF" position.
With the system on, the collectors should be purged of air
in 1 to 3 minutes and the water returning to the pool should
be clear and free from air bubbles. After 5 minutes, feel
the return end of the absorber plate on each collector. They
should be uniformly cool to the touch. If they are, you have
uniform flow to all collectors. If they are not, flow must
be increased to the minimum specified levels in order to get
rated performance from the system. If on a multiple-row system,
one bank feels warmer than the other, the flow must be corrected.
Install a ball valve in either the supply or return line to
the row that feels cooler. You can then throttle this valve
until the temperatures of the collectors on each bank are
approximately equal.
Next, switch the control to "OFF". The valve should
turn to divert the water to the pipe that by-passes the solar
collectors. Switch the control to "AUTO". Set the
temperature control to the maximum position, or at least 10
degrees higher than the pool water temperature. The "Heating"
light should come on and the valve should turn to divert all
the pool water through the solar system. If the light does
not come on, disconnect the pool water temperature sensor
wires and temporarily "short" the solar sensor terminals.
If the "Heating" light now comes on, you probably
have a bad wiring connection to the solar sensor.
Set the temperature control to the minimum position or at
least 10 degrees below the pool water temperature. The "Heating"
light should go out and the valve should turn to divert the
water through the by-pass pipe. If it does not, disconnect
the solar sensor wires and temporarily "short" the
pool water temperature sensor terminals. If the light now
goes out, you probable have a bad connection in the pool water
sensor wiring. For further trouble shooting information, see
the control and valve manuals packed with the control.
Once everything is working, set the control for the maximum
desired water temperature with the control on "Auto"
and enjoy your pool.
|
|
Maintenance - For pools that are closed during the
winter months, if the solar system is piped in accordance
with the instructions in this manual, it will naturally drain
by gravity after the pump has been turned off. When all water
has drained from the collector system you may follow normal
pool winterization procedures. Any piping that will not drain
by gravity must be manually drained or blown out, to prevent
freeze damage. Low areas that can trap water should be filled
with propylene glycol to prevent freezing.
For pools remaining open during the winter months, isolation
valves may be installed as shown in Fig. 3. After the solar
system is completely drained shut off the ball valve to isolate
the system.
In warm climates where the pool is kept open all year a normal
practice is to turn on the filter system with the solar system
on, sending warm pool water to the collectors whenever light
freezes are expected. Your control can be easily set to automate
this operation whenever the pump is running. Contact the factory
for details. Obviously, an automatic recirculation system
works only when electricity is available.
|
|
Installation on a Tile roof Be careful not to break
the tile. Do not walk on the high points of barrel tiles.
At each mounting bracket location, drill through the high
point on the tile with a masonry drill slightly larger than
the screw (9/32 for ¼-inch screw). Then drill through
the roof board with a pilot drill for the screw (1/8 for #14
screw). Attach a 5/4x4 or 1x4 pressure treated board to the
roof and screw the mounting brackets to it. Use screws long
enough to penetrate the roof boards and coat the threads heavily
with Silicone II or RTV before installing them. At the strap
bracket locations, attach 5/4x4 or 1x4 pressure treated boards
to the roof as above and screw the Strap brackets to them.
|
|
Collector Repair - This method allows for an easy
and permanent on-site repair of a collector by isolating the
leaking riser tube, using HI-Deluxe repair kit Part No.1122.
Referring to figure 9, locate the tube to be isolated. (End
tube has been shown for clarity.) Using a sharp utility knife,
very carefully cut away approximately 1" of the tube
at both headers. Drive a screw into the hole in each header.
DO NOT OVERTIGHTEN! This repair method will not void the collector
warranty.
|
 |
|